Case Studies: Office
Active HEPA+
Location:
Commercial Office Space
- Product : Active HEPA+
- Technologies: PCO/BPI/HEPA/ODOGard
- Test time: 5 days total – measured in real time
- Test space: 1240 sq.ft. commercial office
- Test administrator: IAQS
Results : >99.9% reduction airborne mold, bacteria, TVOC, and 99.9% reduction surface bacteria and odors
“It is my considered observation that over the duration of this study, with the expected environmental fluctuations that occurred in a real-time setting, this study indicates that Active HEPA+ coupled with a standard MERV 10 HVAC filter at minimal air turns per hour produces results that substantiate an overall high degree of efficacy. This high rate of efficacy was achieved within the first 24 hours of operation even at lower air turn rates. This would not be expected or typical.”
Ozone levels throughout the duration of the test remained below TLV guidance and below levels measured outdoors.
[fsn_row][fsn_column width=”10″][fsn_text][/fsn_text][fsn_component][/fsn_component][/fsn_column][/fsn_row]
TEST RESULTS:
NAME | TYPE | REDUCED |
Mold Spores | Airborne | >99.90% |
Mold Spores | Surface | 41.00% |
Bacteria Counts | Airborne | >99.90% |
Bacteria Counts | Surface | >99.90% |
TVOC | Airborne | >99.90% |
HCHO (fomaldehyde) | Airborne | >99.90% |
PM 2.5/10.0 | Airborne | 85.50% |
Respirable Particle Counts | Airborne | 80.00% |
Odor Intensity | Airborne | >99.90% |
pureAir HVAC
Location:
Commercial Office Space
- Product : pureAir HVAC
- Technologies: PCO/BPI
- Test time: 5 days total – real time measure
- Test space: Office
- Test administrator: IAQS
95% Reduction Airborne Mold, Bacteria, TVOC, and 90% Reduction Surface Bacteria
“It is my considered observation that pureAir HVAC does provide a rapid and significant reduction of the typical contaminants tested. The levels achieved and maintained during this test were far below any known standard or established TLV. It is my considered opinion that this sustained condition would not be typical or possible without the continuous use of this product.” – Keith Roe, IAQS
Ozone levels throughout the duration of the test remained below TLV guidance and below levels measured outdoors.
[fsn_row][fsn_column width=”10″][fsn_text][/fsn_text][fsn_component][/fsn_component][/fsn_column][/fsn_row] [fsn_row][fsn_column width=”10″][fsn_text][/fsn_text][fsn_component][/fsn_component][/fsn_column][/fsn_row]
TEST RESULTS:
NAME | TYPE | REDUCED |
Mold Spores | Airborne | >99.99% |
Mold Spores | Surface | 50.00% |
Bacteria Counts | Airborne | >95.00% |
Bacteria Counts | Surface | 90.00% |
TVOC | Airborne | >99.00% |
HCHO (formaldehyde) | Airborne | >99.90% |
PM 2.5/10.0 | Airborne | >61.00% |
Respirable Particle Counts | Airborne | >62.00% |
pureAir HVAC (50% O3)
Location:
Commercial Office Space
- Product : pureAir HVAC
- Technologies: PCO/BPI/O3
- Test time: 5 days total – real time measure
- Test space: Office 1240 sq. ft.
- Test administrator: IAQS
Results: >99.9% reduction Airborne Mold and TVOC
“It is my considered observation that pureAir HVAC does provide a rapid and significant reduction of the typical contaminants tested. The levels achieved were below any known standard or recommended TLV. In my considered opinion, the sustained condition would not be achievable without the continual use of the technology represented. “
– Keith Roe, IAQS
Ozone levels throughout the duration of the test remained below TLV guidance and below levels measured outdoors.
[fsn_row][fsn_column width=”10″][fsn_text][/fsn_text][fsn_component][/fsn_component][/fsn_column][/fsn_row] [fsn_row][fsn_column width=”10″][fsn_text][/fsn_text][fsn_component][/fsn_component][/fsn_column][/fsn_row]
TEST RESULTS:
NAME | TYPE | REDUCED |
Mold Spores | Airborne | >99.99% |
Mold Spores | Surface | 66.00% |
Bacteria Counts | Airborne | NA (high RH)* |
Bacteria Counts | Surface | 75.00% |
TVOC | Airborne | >99.00% |
HCHO (formaldehyde) | Airborne | >99.00% |
PM 2.5/10.0 | Airborne | 50.00% |
Respirable Particle Counts | Airborne | 43.00% |
pureAir HVAC ODOGard MERV 13
Location:
Commercial Office Space
- Product : pureAir HVAC + treated filter
- Technologies: PCO/BPI/ODOGard
- Test time: 5 days total – measured in real time
- Test space: 1240 sq.ft. commercial office
- Test administrator: IAQS
Results: >99.9% reduction Airborne Mold, Bacteria, TVOC, and Odor
“It is my considered observation that pureAir HVAC in combination with an ODOGard coated filter does provide a rapid and significant reduction of the typical air and surface contaminants tested. In my considered opinion, the sustained condition would not be achievable without the continual use of the technology represented.“
– Keith Roe, IAQS
Ozone levels were 0 ppm throughout the duration of the test.
[fsn_row][fsn_column width=”10″][fsn_text][/fsn_text][fsn_component][/fsn_component][/fsn_column][/fsn_row] [fsn_row][fsn_column width=”10″][fsn_text][/fsn_text][fsn_component][/fsn_component][/fsn_column][/fsn_row]
TEST RESULTS:
NAME | TYPE | REDUCED |
Mold Spores | Airborne | >99.94% |
Bacteria Counts | Airborne | >99.99% |
TVOC | Airborne | >99.99% |
HCHO (formaldehyde) | Airborne | >99.99% |
Odor Intensity | Airborne | >99.99% |
750 Wall Mount & ODOGard Pre-filter
Location:
Commercial Office Space
- Product : 750 Wall Mount
- Technologies: PCO/BPI/ODOGard
- Test time: 5 days total – measured in real time
- Test space: 1240 sq.ft. commercial office
- Test administrator: IAQS
Results: >97.0% reduction surface mold and bacteria and 90.0% reduction airborne mold and TVOC
“It is my considered observation that Greentech 750 in combination with an ODOGard coated pre-filter does provide a significant reduction of the typical air and surface contaminants tested. ASHRAE provides guidance as to the use of supplemental air purification and disinfection equipment after increasing fresh air ventilation rate to a minimum of 6 air changes per hour and filtration levels to a MERV 13 level. This study was performed without those improvements. It is my considered opinion that if this unit was used within the current ASHRAE guidelines an even greater efficacy could be expected.” – Keith Roe, IAQS
Ozone levels were 0 ppm throughout the duration of the test
TEST RESULTS:
NAME | TYPE | REDUCED |
Mold Spores | Airborne | 93.00% |
Mold Spores | Surface | 97.00% |
Bacteria Counts | Airborne | 63.00% |
Bacteria Counts | Surface | 97.50% |
TVOC | Airborne | 92.00% |
HCHO (formaldehyde) | Airborne | 94.00% |
pureAir 3000+
Location:
Commercial Office Space
- Product : pureAir 3000+
- Technologies: PCO/ODOGard
- Test time: 5 days total – measured in real time
- Test space: Commercial office
- Test administrator: IAQS
Results: >90.0% reduction RPC
“The sustained significant reduction of PM contaminants in the test area would not be expected or typical. This would demonstrate the effectiveness of the active passive technology provided by the Greentech unit. These lowered results were not exhibited in the indoor control area readings without the equipment.” – Keith Roe, IAQS
There was no detectable level of ozone.
TEST RESULTS:
NAME | TYPE | REDUCED |
PM 2.5/10.0 | Airborne | 64.00% |
Respirable Body Counts | Airborne | 90.00% |
pureAir 3000+
Location:
Nail Salon Commercial Office Space
- Product : pureAir 3000+
- Technologies: PCO/ODOGard
- Test time: 5 days total – measured in real time
- Test space: 1200^2ft. nail salon
- Test administrator: IAQS
Results : 83% reduction RPC and 60% reduction TVOC
“Nail salons are a harsh indoor air environment, with contaminants continuously being introduced. Both qualitatively and quantitatively, there was a measurable and significant decrease in all air pollutants monitored as well as the presence of odors. The ongoing source of air pollutants was ever changing and fluctuating in intensity, but the decreases that were reported were during the working day when they collectively were at their peak.” – Keith Roe, IAQS
There was no detectable level of ozone.
TEST RESULTS:
NAME | TYPE | REDUCED |
TVOC | Airborne | 60.00% |
HCHO (formaldehyde) | Airborne | 57.00% |
Respirable Particle Counts | Airborne | 83.00% |
PM 2.5 | Airborne | 68.00% |
PM 10.0 | Airborne | 78.00% |
pureAir 3000 Classic
Location:
Commercial Office Space
- Product : pureAir 3000 Classic
- Technologies: PCO/BPI/ODOGard
- Test time: 5 days total – measured in real time
- Test space: Commercial office
- Test administrator: IAQS
Results : 99.98% inactivation of SARS-CoV-2
“The areas tested within this commercial building were found to have a very acceptable Indoor air quality as compared to most testing projects performed. However, it was my findings, that the Respirable Particle Counts, PM2.5/10.0 and mold spores were significantly reduced even further in the highlighted areas. It would be my considered opinion that this additional reduction would not be expected or typical without the use of the Greentech Technology.
– Keith Roe, IAQS
There was no detectable level of ozone.
1250 Wall Mount
Location:
Commercial Office Space
- Product : 1250 wall mount
- Technologies: PCO/BPI/O3
- Test time: 5 days total – measured in real time
- Test space: Commercial office
- Test administrator: IAQS
Results : 71.0% reduction RPC
“The areas tested within this commercial building were found to have a very acceptable Indoor air quality as compared to most testing projects performed. However, it was my findings, that the Respirable Particle Counts, PM2.5/10.0 and mold spores were significantly reduced even further in the highlighted areas. It would be my considered opinion that this additional reduction would not be expected or typical without the use of the Greentech Technology.”
– Keith Roe, IAQS
There was no detectable level of ozone.
TEST RESULTS:
NAME | TYPE | REDUCED |
Respirable Body Counts | Airborne | 71.00% |